Authors :
Tsanta Fifaliana Andriamihaja Ramilison; Solofo Hery Rakotoniaina; Harlin Samuel Andriatsihoarana
Volume/Issue :
Volume 11 - 2026, Issue 11 - November
Google Scholar :
https://tinyurl.com/y8bxr2fe
DOI :
https://doi.org/10.38124/ijisrt/26nov472
Note : A published paper may take 4-5
working days from the publication date to appear in PlumX Metrics, Semantic Scholar, and
ResearchGate.
Abstract :
Single wire earth return power lines use the ground as the normal path for return current. Their operating performance and response to faults therefore depend on soil properties. Conventional models generally assume homogeneous soil, although soil resistivity can vary with depth and along the line route. This study proposes an electrical model that accounts for both types of variation. An eighty-kilometer line is divided into ten longitudinal zones, and the Martins Britto formulation is used to represent the layered soil in each zone by an equivalent complex conductivity. The self and mutual impedances are then calculated for each zone. The loop impedance is obtained by subtracting twice the mutual impedance from the sum of the two self-impedances. The Carson formulation serves as the reference, while the Deri approximation supplies the parameters for simulations in Simulink. The model represents the earth return path in heterogeneous soils and supports preliminary engineering and safety assessments. Field measurements are needed to validate the model for a specific site.
Keywords :
Soils Heterogeneity, Soils Stratification, Ground-Return Impedance, Grounding Electrodes.
References :
- N. Hosseinzadeh, J. E. Mayer, and P. J. Wolfs, “Rural single wire earth returns distribution networks: Associated problems and cost-effective solutions,” Int. J. Electr. Power Energy Syst., vol. 33, 2011.
- A. C. Britten, “Single-wire earth return systems in Eskom,” in Proc. African Utility Week, South Africa.
- M. A. Kashem and G. Ledwich, “Distributed generation as voltage support for single wire earth return systems,” IEEE Trans. Power Deliv., vol. 19, no. 3, pp. 1002–1011, Jul. 2004, doi: 10.1109/TPWRD.2003.822977.
- G. Bakkabulindi, M. R. Hesamzadeh, M. Amelin, and I. N. Da Silva, “Models for conductor size selection in single wire earth return distribution networks,” IEEE Trans. Power Deliv., 2013.
- J. R. Carson, “Wave propagation in overhead wires with ground return,” Bell Syst. Tech. J., vol. 5, no. 4, pp. 539–554, 1926.
- A. Deri, G. Tevan, A. Semlyen, and A. Castanheira, “The complex ground return plane: A simplified model for homogeneous and multi-layer earth return,” IEEE Trans. Power App. Syst., vol. PAS-100, no. 8, pp. 3686–3693, 1981.
- M. Nakagawa, A. Ametani, and K. Iwamoto, “Further studies on wave propagation in overhead lines with earth return: Impedance of stratified earth,” Proc. Inst. Electr. Eng., vol. 120, 1973.
- T. Noda, “A double logarithmic approximation of Carson’s ground-return impedance,” IEEE Trans. Power Deliv., vol. 21, no. 1, pp. 472–479, Jan. 2006.
- I. Kim, “A new single-logarithmic approximation of Carson’s ground-return impedances—Part 1,” IEEE Access, vol. 9, 2021, doi: 10.1109/ACCESS.2021.3097377.
- A. G. Martins-Britto, F. V. Lopes, and S. R. M. J. Rondineau, “Multi-layer earth structure approximation by a homogeneous conductivity soil for ground return impedance calculations,” IEEE Trans. Power Deliv., 2020, doi: 10.1109/TPWRD.2019.2930406.
- B. Nkom, A. P. R. Taylor, and C. Baguley, “Narrowband modeling of single-wire earth return distribution lines,” IEEE Trans. Power Deliv., vol. 33, no. 4, pp. 1565–1575, Aug. 2018.
- H. B. Dwight, “Calculation of resistances to ground,” Electr. Eng., vol. 55, no. 12, pp. 1319–1328, 1936.
- A. Semlyen and A. Deri, “Time domain modelling of frequency dependent three-phase transmission line impedance,” IEEE Trans. Power App. Syst., vol. PAS-104, 1985.
- A. Ametani, N. Nagaoka, Y. Baba, and T. Ohno, Power System Transients: Theory and Applications. Boca Raton, FL, USA: CRC Press, 2014.
- IEEE Guide for Safety in AC Substation Grounding, IEEE Std 80-2013, 2013.
- A. Ametani, N. Nagaoka, Y. Baba, and T. Ohno, Power System Transients: Theory and Applications. Boca Raton, FL, USA: CRC Press, 2014.
Single wire earth return power lines use the ground as the normal path for return current. Their operating performance and response to faults therefore depend on soil properties. Conventional models generally assume homogeneous soil, although soil resistivity can vary with depth and along the line route. This study proposes an electrical model that accounts for both types of variation. An eighty-kilometer line is divided into ten longitudinal zones, and the Martins Britto formulation is used to represent the layered soil in each zone by an equivalent complex conductivity. The self and mutual impedances are then calculated for each zone. The loop impedance is obtained by subtracting twice the mutual impedance from the sum of the two self-impedances. The Carson formulation serves as the reference, while the Deri approximation supplies the parameters for simulations in Simulink. The model represents the earth return path in heterogeneous soils and supports preliminary engineering and safety assessments. Field measurements are needed to validate the model for a specific site.
Keywords :
Soils Heterogeneity, Soils Stratification, Ground-Return Impedance, Grounding Electrodes.